The ultimate in water treatment control flexibility
DULCOMETER diaLog X continuously monitors and controls a wide range of measured parameters and digital inputs to optimize the water treatment process. The DULCOMETER diaLog X can control and monitor metering pumps, valves, motors, and other output components to provide full automation of your system using the different parameters or measured variables The physical variables to be determined by measuring. more in the glossary through the various inputs. Control of these various devices is accomplished through flexible programing of the open platform controller via multiple standards, connectivity options and communications protocols.
Features and Benefits
- Excellent flexibility thanks to modular construction and easily extendible IO modules (input/output), allowing more sensors and pumps to be connected.
- Up to two satellite units can be added for additional inputs and outputs, allowing more sensors and pumps to be connected.
- Intuitive operation via the HMI (Human-Machine Interface) thanks to a clearly legible industrial display and robust keys for standard commands, such as calibration and monitoring.
- Simple configuration of process settings as well as monitoring and visualisation of process data via a web server with freely configurable and preconfigured software modules.
- Extensive overview and control of processes, e.g. cooling tower processes: All process data and alarms can be communicated to the process control system via fieldbuses such as Modbus RTU.
- Advanced communication options: Various network protocols such as FTP or MQTT enable remote access and data management via Wi-Fi and LAN (Ethernet).
Field of application
The following list is a general representation of basically suitable applications for this product. Please contact your personal representative to discuss the use of the product in your individual application.
- Potable water and sewage treatment
- Wastewater treatment
- Industrial and process water treatment
- Food and Beverage process water treatment
Technical Details
Comprehensive inputs and outputs
- Up to 24 flexible sensor inputs and mA outputs (8 per device), e.g. CTFS sensor, linear polarisation resistor (LPR) corrosion sensor
- Up to 30 output relays and pulse outputs (10 per device) to control pumps and other actuators
- Up to 24 digital inputs (8 per device) to control level switches, water meters and remote switches
- Up to 12 pulse frequency outputs
- Up to 18 relays
Communication options
- In-built Modbus RTU and via gateways (BACnet, Modbus TCP, PROFINET)
- Web interface via Wi-Fi and Ethernet, FTP server, rest API, MQTT client interface. The client interface is an intuitive remote control via a Wi-Fi or network connection to your PC or smartphone, e.g. for configuration settings or setpoint settings.
- Configurable and managed via DULCONNEX.
Technical Data
|
Measured variables and measuring ranges | Conductivity: With digital sensor CTFS at input A and B and via serial module D1: 0.1 - 10 mS/cm Via conductivity module L3 depending on sensor used (LMP, LFT): 50 μS cm - 20 mS/cm Via mA module AA with the inductive conductivity sensor ICT: 8 to 2 mS/cm, 20 mS/cm, 200 mS/cm Type of connection mV: pH: 0.00 ... 14.00 ORP potential: -1,500 ... +1,500 mV Type of connection mA (amperometric measured variables, measuring ranges corresponding to sensors, 2 ppm, 10 ppm): Chlorine Chlorine dioxide Chlorite Bromine Ozone Hydrogen peroxide Peracetic acid Temperature: via Pt 100/Pt 1000, measuring range 32 … 302 °F (0 … 150 °C) |
Inputs and outputs | Inputs 4 plug-in module slots per unit for 2-channel serial sensor input module 2-channel conductivity input module 2-channel mV input module 2-channel mV/mA input module 2-channel mA input module Outputs 2-channel mA output module 6 output relays as changeover contacts, of which 3 are potential-free and 3 are AC/DC 4 pulse frequency outputs for controlling metering pumps 8 digital control inputs for contact water meter, flow switch and pause for locking |
Resolution | pH: 0.01 pH ORP: 1 mV Amperometric analysis (chlorine etc.): 0.001/0.01 ppm, 0.01 vol. % |
Accuracy | 0.3% based on the full-scale reading |
Temperature compensation | Pt 100/Pt 1000 for pH |
Control characteristic | P/PI/PID control |
Electrical Connection | 100 – 230 V, 50/60 Hz |
Ambient temperature | 23 … 122 °F (-5 … 50 °C) at max. 95% relative air humidity (non-condensing) |
Tests and approvals | CE, MET, UK CA |
Housing material | PC with flame proofing equipment |
Dimensions | 10.87 x 16.69 x 5.39 in (H x W x D) |
Enclosure rating | Wall-mounted: IP 67 |
Field bus connection | Modbus RTU, additional field buses via gateway |
Service Unavailable